F074 Safe area / Intrinsically safe – Level / Pump Controller

The F074 is a basic level indicator / pump controller that works with a preset value and two switch points to control a pump or valve. The low and high level switch points are entered as a percentage of the preset value to switch the device on / off.

F074-DATA-EN-V2607
Datasheet

Measure. Monitor. Repeat.

For better insights, better decision-making and better process performance.

Key Features & Benefits

  • The display shows the actual level, preset value, high / low switch points and status.
  • On-screen engineering units are easily configured from a comprehensive selection.
  • Selectable on-screen engineering units for level: ml, L, m³, GAL, USGAL, kg, lb, bbl or no unit.
  • Selectable on-screen engineering units for height: mm, cm, m, mtr, inch, ft, mmwk, mmwc, cmwk, cmwc, mwk, mwc, inwc, ftwc, mBar, Bar, PSI or no unit.
  • Level: six large 17mm (0.67″) digits.
  • LED backlight with adjustable intensity.
  • Level control: high / low switch points and a preset value can be set.
  • Switch points and preset value can be set by the operator or they can be password protected.
  • One control output for on / off pump or value control.
  • Intrinsically safe according ATEX, IECEx and CSA C-US.
  • GRP, Aluminum or high grade stainless steel enclosure.
  • Auto backup of settings in EEPROM memory.
  • Easy configuration with clear alphanumerical display.
  • Ambient temperature: -40°C to +70°C (-40°F to 158°F).

Typical Applications

  • Basic on / off level control applications without PI(D) control requirements. Also very suitable for applications where the required level changes frequently.
  • Functions for filling-up a container or emptying a well or tank.
  • The F-Series is your first and best choice for field mount indicators in safe and hazardous area applications. Especially in harsh weather conditions like rain, snow, sandy deserts, salty atmospheres and temperatures between -40°C up to +70°C (-40°F up to 158°F).

Advantages

  • Robust aluminum or stainless steel 316L field enclosure (IP65, IP67 / NEMA Type4X) .
    It is so rugged, a truck can even stand on it!
  • Intrinsically Safe available - ATEX, IECEx and CSA approval for gas and dust applications.
  • Familiar easy operation with the Fluidwell "Know one, know them all" configuration structure, saving time, cost and aggravation.
  • Very diverse mounting possibilities: walls, pipes, panels or directly onto outdoor sensors.
CategoryFunction / DescriptionType / Details
Signal InputsLevel Inputs(0)4–20mA
Alarm / Analog OutputsNone
Control OutputsFunctionControl output to operate a pump or valve according to high / low level switch point values.
Type: One passive NPN transistor, active PNP transistor, or isolated electro-mechanical relay.
SupplyPower SupplyLong life Lithium battery.
4–20mA input Loop-powered.
8–24V AC/DC.
115–230V AC.
Basic: 8–30V DC
Sensor Supply8.2V, 12V, 24V DC
Hazardous Area – Intrinsically SafeATEX: Gas: II 1 G Ex ia IIC T4 Ga
Dust: II 1 D Ex ia IIIC T200 100 °C Da
IECEx: Gas: Ex ia IIC T4 Ga
Dust: Ex ia IIIC T200 100 °C Da
CSA: I.S. Class I/II/III, Div 1, Grp A…G, T4; Class I, Zone 0, AEx ia IIC T4 Ga
Note: Extended aluminum enclosures not available with CSA/FM approval.
Explosion ProofATEX/IECEx: Gas: II 2 G Ex db IIB+H2 T5 Gb
Dust: II 2 D Ex tb IIIC T80°C Db
CommunicationModbus communication available on F1-Series products.
HART communication available with F018 Flow rate Monitor / Totalizer.

Modbus Communication MODBUS communication with Fluidwell F1xx
Declaration of ConformityEU Declaration of Conformity F1 2019-01
Battery Information SheetMSDS Battery-Information-Sheet (8)
F Series Brochure FSERIES-LEAFLET-EN-V2534 (1)

Why Choose Process Networks?

ISO-Certified Quality

Our ISO 9001:2015 quality management system ensures full traceability across design, installation, calibration and support.

Technical Expertise You Can Reach

When you contact us, you speak directly to an expert — not a call centre.

Trusted Supplier Partnerships

Exclusive access to premium instrumentation from leading global manufacturers in Germany, Japan, the US and across Europe.

Long-Term Support & SLAs

Most customers stay with us for years because we stay with them providing ongoing maintenance, calibration and on-site service.

Proven Field Experience

Thousands of instruments installed and tens of thousands points monitored daily on systems we support.

Speak to a technical expert about this product

Our experts will guide you to the right solution whether you need a single sensor or a site-wide monitoring system.

Office

Process Networks Ltd,
Unit K20 Drinan Enterprise Centre,
Swords, Co. Dublin, K67 NN59

Call

(01) 211 8414

Email

info@processnetworks.ie

    By submitting your enquiry, you agree to receive updates from Process Networks in accordance with our Privacy Policy.