MTP 200-TE

The universal transmitter MTP200i-TE converts various different input signals (mA, V, PT100, potentiometer, thermocouples, Thermocouple-resistance). The configuration can be done simply via our software. An electrically isolated mA / V output is available. Alarm monitoring takes place by two relay contacts and one transistor output. Additional another relay contact output is available for signalizing the safety functions. All output circuits can be used in safety circuits and are galvanic isolated from each other and from the power supply.

Measures: Voltage

MTP200-TE-brochure
Datasheet

Measure. Monitor. Repeat.

For better insights, better decision-making and better process performance.

Key Features & Benefits

  • SIL2-Transmitter in DuoTec-Failsafe Technology with self-monitoring
  • Inputs: Resistor and Pt100 with 2-, 3- and 4-wire switch, all types of thermocouple, current, voltage
  • Analogue output for mA and V
  • 3 individually adjustable limit values
  • 1 service alarm
  • Gradient alarm function
  • Square root of the output signal
  • Safe galvanic separation

MTP 200-TE

Simple Operation

  • Configuration / visualization software WINSMART
  • Diagnostic manager with fault memory
  • BUS-Integration (RS 232 and RS 485)
  • Power supply via DIN rail or terminal
  • Simple assembling

Function

  • Universal measuring transmitter in DuoTec-Failsafe Technology with self-monitoring
  • Certified according to IEC 61508 SIL2
  • Input: Resistor and Pt100 with 2-, 3- and 4-wire switch, all types of thermocouple, current, voltage
  • Output: 0/4-20 mA, 1-5/0-10 VDC, square rootable
  • 3 individually adjustable limit values
    (2 relays contact outputs, 1 transistor output)
  • 1 service alarm
  • Galvanic separated between auxiliary energy, input and output(3 Port separation)
  • Executed on Namur recommendation NE 21
  • RS 485 bus connection via mounting rail bus connector
  • PC-connection via MÜTEC interface cable at the front
  • Configuration ON-LINE by MÜTEC-WINSMART software
  • Auxiliary energy: 24VDC/AC
  • Form of construction: DIN-Rail mounting, DIN EN 50022
CategorySpecification
Analogue Inputs (AI1 – AI4)First-order filter configurable (0.1 – 99.9)
AI1 – mA InputMeasuring range: -22…22 mA (configurable)
Input resistance: 115 Ω
AI2 – Voltage InputMeasuring range: -11…+11 V (configurable)
Input resistance: 100 kΩ
AI3 – Pt100 Input (DIN IEC 751)2-, 3-, 4-wire connection
Measuring range: -200…+800 °C
Scale range: 5…1000 °C
Measuring current: 1 mA
Resolution: 0.01 K
Max. loop resistance: 100 Ω
AI3 – Resistance / Potentiometer Input (DIN 43822)2-, 3-, 4-wire connection
Measuring range: 0…600 Ω or 0…5000 Ω
Scale range: 3…600 Ω or 3…5000 Ω
Measuring current: 1 / 0.2 mA
Resolution: 0.01 / 0.1 Ω
Max. loop resistance: 100 Ω
AI4 – mV / Thermocouple InputMeasuring range: -70…+70 mV (configurable)
Input resistance: >10 MΩ
Max. loop resistance: 2000 Ω
Thermocouple types: B, E, J, K, L, R, S, T, U
Analogue Output (AO)Galvanically isolated
Ranges: 0…22 mA, 0…11 V
Standard: 0/4–20 mA, 0/2–10 V
Load: ≤500 Ω at 20 mA, ≥50 kΩ (voltage)
Accuracy: 0.02% of final value
Rise time: <150 ms
Contact Outputs2× relay (REL1, REL2) + 1× transistor output (DO)
3 independently configurable alarms
Alarm delay: 0…9.9 s
Hysteresis: 0…99.9%
Operating mode: NO / NC
Relay Outputs (REL1 / REL2)Switching power: max. 62.5 VA / 30 W
Switching voltage: max. 125 VAC / 110 VDC
Switching current: max. 1 A
Contact material: AgPd + 10 µAu
Transistor Output (DO)Switching voltage: <28 VDC
Switching current: <50 mA
Switching power: <1.4 W
Maintenance Output (REL3)Normally closed
Indicates maintenance requirement
Red LED indication
SupplySupply voltage: 19…30 VDC or 18…28 VAC
Power consumption: 1.2 W (4 mA) / 1.5 W (20 mA)
Green LED status indication
InterfacesCOM / RS232 via front socket
RS485 half duplex
Baud rate: 9600 bps
Device address: 1–248
General AccuracyTypical: <0.02% of final value
Maximum: <0.04% of final value
Temperature CoefficientTypical: <0.005%/K
Maximum: <0.01%/K
Ambient ConditionsOperation: -20 °C … +60 °C
Storage: -30 °C … +80 °C
Humidity: 10…95% r.H. (non-condensing)
HousingMaterial: PBT
Protection class: IP20
Flammability: UL94 V0
Dimensions: 22.5 × 114.5 × 99 mm
Weight: 250 g
DIN-rail mounting
ConformityATEX: EN 60079-0, EN 60079-11, EN 60079-26
EMC: EN 61000-6-2, EN 61000-6-4, EN 61326-1
Optional: ATEX [Ex ia] IIC

Operating Instructions 125_BAMTP200iTESILDE-EN
SIL datasheetSIL-Zertifikat-MTP

Why Choose Process Networks?

ISO-Certified Quality

Our ISO 9001:2015 quality management system ensures full traceability across design, installation, calibration and support.

Technical Expertise You Can Reach

When you contact us, you speak directly to an expert — not a call centre.

Trusted Supplier Partnerships

Exclusive access to premium instrumentation from leading global manufacturers in Germany, Japan, the US and across Europe.

Long-Term Support & SLAs

Most customers stay with us for years because we stay with them providing ongoing maintenance, calibration and on-site service.

Proven Field Experience

Thousands of instruments installed and tens of thousands points monitored daily on systems we support.

Speak to a technical expert about this product

Our experts will guide you to the right solution whether you need a single sensor or a site-wide monitoring system.

Office

Process Networks Ltd,
Unit K20 Drinan Enterprise Centre,
Swords, Co. Dublin, K67 NN59

Call

(01) 211 8414

Email

info@processnetworks.ie