F011 Safe area / Intrinsically safe – Totalizer
The F011 is a local totalizer which displays the running total and accumulated total simultaneously. Total can be reset to zero by pressing the CLEAR button twice.
Measure. Monitor. Repeat.
For better insights, better decision-making and better process performance.
Key Features & Benefits
- Displays total and accumulated total simultaneously.
- Total – resettable: seven 17mm (0.67″) digits.
- Accumulated total – not resettable: eleven 8mm (0.31″) digits.
- Selectable on-screen engineering units for total: ml, L, m³, GAL, USGAL, kg, lb, bbl or no unit.
- LED backlight with adjustable intensity.
- Auto backup of settings and running totals in EEPROM memory.
- Intrinsically safe according ATEX, IECEx and CSA C-US.
- GRP, Aluminum or high grade stainless steel enclosure.
- Easy configuration with clear alphanumerical display.
- Ambient temperature: -40°C to +70°C (-40°F to 158°F).
- Various accessories are available for this product
Typical Applications
- Flow measurement where a local totalizer function is required without flow rate or signal re-transmission functionality.
- The F-Series is your first and best choice for field mount indicators in safe and hazardous area applications. Especially in harsh weather conditions like rain, snow, sandy deserts, salty atmospheres and temperatures between -40°C up to +70°C (-40°F up to 158°F).
Advantages
- Robust aluminum or stainless steel 316L field enclosure (IP65, IP67 / NEMA Type4X) .
It is so rugged, a truck can even stand on it! - Intrinsically Safe available - ATEX, IECEx and CSA approval for gas and dust applications.
- Familiar easy operation with the Fluidwell "Know one, know them all" configuration structure, saving time, cost and aggravation.
- Very diverse mounting possibilities: walls, pipes, panels or directly onto outdoor sensors.
| Category | Function / Description | Type / Details |
|---|---|---|
| Signal Inputs | Flowmeter Inputs |
Pulse type inputs: Reed-switch, NAMUR, NPN/PNP pulse, Sine wave (coil), active pulse signal. (0)4–20mA |
| Pulse Outputs | None | |
| Analog / Alarm Outputs | None | |
| Supply | Power Supply |
Long life Lithium battery. 4–20mA input Loop-powered. 8–24V AC/DC. 115–230V AC. Basic: 8–30V DC |
| Sensor Supply | 3.2V, 8.2V, 12V, 24V DC | |
| Hazardous Area – Intrinsically Safe |
ATEX: Gas: II 1 G Ex ia IIC T4 Ga Dust: II 1 D Ex ia IIIC T200 100 °C Da IECEx: Gas: Ex ia IIC T4 Ga Dust: Ex ia IIIC T200 100 °C Da CSA: I.S. Class I/II/III, Div 1, Grp A…G, T4; Class I, Zone 0, AEx ia IIC T4 Ga Note: Extended aluminum enclosures not available with CSA/FM approval. | |
| Explosion Proof |
ATEX/IECEx: Gas: II 2 G Ex db IIB+H2 T5 Gb Dust: II 2 D Ex tb IIIC T80°C Db | |
| Communication |
Modbus communication available on F1-Series products. HART communication available with F018 Flow rate Monitor / Totalizer. | |
Why Choose Process Networks?

ISO-Certified Quality
Our ISO 9001:2015 quality management system ensures full traceability across design, installation, calibration and support.

Technical Expertise You Can Reach
When you contact us, you speak directly to an expert — not a call centre.

Trusted Supplier Partnerships
Exclusive access to premium instrumentation from leading global manufacturers in Germany, Japan, the US and across Europe.

Long-Term Support & SLAs
Most customers stay with us for years because we stay with them providing ongoing maintenance, calibration and on-site service.

Proven Field Experience
Thousands of instruments installed and tens of thousands points monitored daily on systems we support.









Speak to a technical expert about this product
Our experts will guide you to the right solution whether you need a single sensor or a site-wide monitoring system.
Office
Process Networks Ltd,
Unit K20 Drinan Enterprise Centre,
Swords, Co. Dublin, K67 NN59
Call
(01) 211 8414
info@processnetworks.ie