MTP 300I-SIL
The fastest SIL2-certified thermocouple transmitter in the world. In high pressure processes like plastic production, in gas turbines and other application, the quick measurement of the temperature is a crucial factor. Especially in LDPE plants, in which rapid decomposition reactions are a dangerous and costly risk, several milliseconds play a significant role for detecting decompositions and preventing damage to the plant
The 2-wire temperature transmitter MTP300i-SIL-* has one, the MTP300-SIL-2* two galvanic isolated thermocouple-inputs. They have been specially developed for rapid temperature measurement in the hazardous area. Each TC-input is equipped with a Pt100 sensor for the cold-junction compensation. The thermocouple transmitter must be intrinsically safe supplied by a repeater power supply or with a ZENER barrier.
More info
Properties
- 2-wire transmitter for thermocouples
- Galvanically isolated measuring inputs with cold-junction compensation
- Signal pass-through time: without Butterworth filter ≤ 3 ms with Butterworth filter ≤ 38 ms
- Installation in zone 1 or 2 permissible
- Intrinsic safety according to EN 60079-11
- SIL 2 according to IEC 61508
- Device type B according to IEC 61508
- Error indication according to NAMUR NE 43
- LED for status indication
| Parameter | Specification |
|---|---|
| Certificate | Ex certificate IECEx BVS 14.0073 X, Ex ib [ia Ga] IIC T4 Gb |
| Functional Safety (SIL) | SIL 2 according to EN 61508 |
| Power Supply – Ex ib IIC (terminals 1 and 4) | Voltage Ui: 28 VDC Current Ii: 95 mA Power Pi: 655 mW Effective inner capacity Ci: 26 nF Effective inner inductivity Li: negligible |
| Thermocouple Input – Ex ia IIC / Ex ib IIC (terminals 5-8, 9-12) | Voltage Uo: 1 VDC Current Io: 1.8 mA Power Po: 0.5 mW Permissible outer capacity Co: 10 μF Permissible outer inductivity Lo: 100 mH |
| Input Signal (terminals 5-8) | Thermocouple type NiCr-Ni K, fixed range (see nameplate), Cold-junction compensation with Pt100 sensor (-10 … +70°C) |
| Output Signal (terminals 1-4) | Current proportional to temperature Io: 4–20 mA, Max current < 24 mA, Behavior by failure Io ≤ 3.6 mA |
| Status Indicator | Green LED: power / mA signal, Off: behavior by failure |
| Signal Pass-through Time | Input to output without Butterworth filter ≤ 3 ms, with filter ≤ 38 ms (default) |
| Transmission Error | Typical < 0.05% (of final value) |
| Temperature Coefficient | Typical < 0.05% / 10 K |
| Pt100 Sensor Error | Class B: ±(0.3°C + 0.005 × t), <0.23°C at 70°C |
| Cold-junction Compensation Error | 0°C–50°C: <0.4°C, -10°C–70°C: <1.0°C |
| Linearization Error | Typical < 0.1°C |
| Measured Value Deviation | Typical < 0.6°C at 20°C |
| Electric Isolation | Tested according to EN 60079-11 |
| Electromagnetic Compatibility | Tested according to EN 61326-3-2 |
| Current Loop Supply | Voltage range (RLoad 70–800 Ω): 12.5–28 V, Current range: >3.5–<24 mA, Power dissipation: Min 50 mW, Max 560 mW |
| Ambient Temperature | Operation: -10°C to +70°C, Storage/Transport: -20°C to +80°C |
| Humidity | Permissible operation: 10–95% r.H, no condensation |
| Housing Material | Polyamide, Light grey |
| Protection Class | IP20 |
| Dimensions | Width × Length × Height: 22.5 × 115 × 108 mm (with terminal blocks) |
| Inflammability Class | UL94 V0 |
| Housing Type for Mounting | 35 mm DIN rails |
| Weight | Approx. 200 g (with terminal blocks) |
| Connection Data | Solid wire: 0.2–2.5 mm² Stranded wire: 0.2–2.5 mm² AWG: 24–14 Stripping length: 7 mm Connection method: pluggable screw connection Tightening torque: 0.5–0.6 Nm |
| Installation | Safe area: Install in clean, dry environment Ex area (zone 1 or 2): Install in suitable housing with minimum IP54 |
Why Choose Process Networks?

ISO-Certified Quality
Our ISO 9001:2015 quality management system ensures full traceability across design, installation, calibration and support.

Technical Expertise You Can Reach
When you contact us, you speak directly to an expert — not a call centre.

Trusted Supplier Partnerships
Exclusive access to premium instrumentation from leading global manufacturers in Germany, Japan, the US and across Europe.

Long-Term Support & SLAs
Most customers stay with us for years because we stay with them providing ongoing maintenance, calibration and on-site service.

Proven Field Experience
Thousands of instruments installed and tens of thousands points monitored daily on systems we support.









Speak to a technical expert about this product
Our experts will guide you to the right solution whether you need a single sensor or a site-wide monitoring system.
Office
Process Networks Ltd,
Unit K20 Drinan Enterprise Centre,
Swords, Co. Dublin, K67 NN59
Call
(01) 211 8414
info@processnetworks.ie