MSK 200-TE
The transmitter power supply unit MSK200i-TE is used for supplying of 2-wire transmitters and for processing of analogue mA-signals. An electrically isolated mA / V output is available. The HART signal connection to the intrinsically safe power supply circuit can be done by using the front socket. Alarm monitoring takes place by two relay contacts and one transistor output. Additional another relay contact output is available for signalizing the safety functions. All output circuits can be used in safety circuits and are galvanic isolated from each other and from the power supply
Measure. Monitor. Repeat.
For better insights, better decision-making and better process performance.
Key Features & Benefits
- SIL2-Transmitter in DuoTec-Failsafe Technology with self-monitoring
- Input for the supply of 2-wire transmitters Input for mA-current
- Analogue output for mA and V
- 3 individually adjustable limit values
- 1 service alarm
- Gradient alarm function
- Square root of the output signal
- Safe galvanic separation

Operation
- Configuration / visualization software WINSMART
- Diagnostic manager with fault memory
- BUS-Integration (RS 232 and RS 485)
- Power supply via DIN rail or terminal
- Simple assembling
Function
The transmitter power supply unit MSK200i-TE is used for supplying of 2-wire transmitters and for processing of analogue mA-signals. An electrically isolated mA / V output is available. The HART signal connection to the intrinsically safe power supply circuit can be done by using the front socket.
More info
Alarm monitoring takes place by two relay contacts and one transistor output. Additional another relay contact output is available for signalizing the safety functions. All output circuits can be used in safety circuits and are galvanic isolated from each other and from the power supply.
| Category | Specification |
|---|---|
| Analogue Input (AI) | First-order filter: 0.1 – 99.9 s (parameterizable) Measuring range: 0…22 mA (configurable) Input resistance: 51 Ω + 2× UD |
| Supply Circuit (SP) | First-order filter: 0.1 – 99.9 s (parameterizable) Umax: 22.4 V at 4 mA load Umin: 17.3 V at 20 mA load Imax: 24 mA Pmax: 360 mW |
| Analogue Output (AO) | Galvanically isolated from input and power supply Output ranges: 0…22 / 22…0 mA, 0…11 / 11…0 V Standard: 0/4–20 mA, 0/2–10 V Load: ≤500 Ω at 20 mA, ≥50 kΩ (voltage) Accuracy: 0.02% of final value Load influence: <0.005% (current), 0.5% at RL=100 kΩ (voltage) Rise time: <150 ms |
| Alarm Outputs | 3 independently adjustable limit values Alarm outputs: 2× relay (REL1, REL2) + 1× transistor (DO) Alarm delay: 0…9.9 s Hysteresis: 0…99.9% Operation mode: operating or zero-current principle |
| Relay Outputs (REL1 / REL2) | Switching power: max. 62.5 VA / 30 W Switching voltage: max. 125 VAC / 110 VDC Switching current: max. 1 A Min. contact voltage/current: 10 mV / 10 µA Contact material: AgPd + 10 µAu |
| Transistor Output (DO) | Switching voltage: <28 VDC Switching current: <50 mA Switching power: <1.4 W |
| Maintenance Output (REL3) | Normally closed contact Maintenance requirement indication Red front LED |
| Power Supply | Supply range: 19…30 VDC or 18…28 VAC Power consumption (feed separator): 1.6 W (4 mA), 2.1 W (20 mA) Power consumption (buffer amplifier): 1.1 W (4 mA), 1.4 W (20 mA) Status indication: Green LED |
| Interfaces | COM / RS232 via front socket RS485 half duplex, no termination Baud rate: 9600 bps Device address: 1–248 HART via supply circuit (0…3 kHz bandwidth) |
| Measurement Accuracy | Typical: <0.025% of final value Maximum: <0.05% of final value |
| Temperature Coefficient | Typical: <0.005%/K Maximum: <0.01%/K |
| Environmental Conditions | Operation: -20 °C … +60 °C Storage: -30 °C … +80 °C Humidity: 10…95% r.H. (non-condensing) |
| Housing | Material: PBT Protection class: IP20 Flammability: UL94 V0 Dimensions: 22.5 × 114.5 × 99 mm (without terminals) Weight: 250 g DIN-rail mounting |
| Conformity | ATEX: EN 60079-0, EN 60079-11, EN 60079-26 EMC: EN 61000-6-2, EN 61000-6-4, EN 61326-1 ATEX data: [EEx ia] IIC |
| ATEX Electrical Data | Power supply circuit: Ui <25.8 V, Ii <65 mA, Pi <420 mW, Co 83 nF, Lo 4 mH mA input circuit: Ui <30 V, Ii <110 mA, Pi <700 mW |
Why Choose Process Networks?

ISO-Certified Quality
Our ISO 9001:2015 quality management system ensures full traceability across design, installation, calibration and support.

Technical Expertise You Can Reach
When you contact us, you speak directly to an expert — not a call centre.

Trusted Supplier Partnerships
Exclusive access to premium instrumentation from leading global manufacturers in Germany, Japan, the US and across Europe.

Long-Term Support & SLAs
Most customers stay with us for years because we stay with them providing ongoing maintenance, calibration and on-site service.

Proven Field Experience
Thousands of instruments installed and tens of thousands points monitored daily on systems we support.









Speak to a technical expert about this product
Our experts will guide you to the right solution whether you need a single sensor or a site-wide monitoring system.
Office
Process Networks Ltd,
Unit K20 Drinan Enterprise Centre,
Swords, Co. Dublin, K67 NN59
Call
(01) 211 8414
info@processnetworks.ie